Operation method |
Cyclic execution of stored program, Time-driven operation, Internal task operation |
|
I/O control method |
Scan synchronized batch processing method (Refresh method) |
Immediate input/output is |
available by ‘Direct I/O’ function |
Program language |
IL (Instruction list) / LD (ladder diagram) / SFC (Sequential function chart) |
|
Number of Instructions |
Operator |
LD: 13, IL: 20 |
|
Standard function |
194 |
|
Standard function block |
12 |
|
Special function block |
Each special module has its own special function block |
|
Processing speed |
Operator |
0.5㎲ / instruction |
|
Standard function/function block |
0.5㎲ / step |
|
Programming memory capacity |
68K |
Built-in flash memory (128K) |
I/O points |
From 10 to 80 points (according to modules) |
|
Data Memory |
Direct variable area (DVA) |
2~8K |
Setting in GMWIN |
Symbolic variable area (SVA) |
32K - Direct variable area |
|
Timer |
No limitation. Time range: 0.001~4294967.295 sec (1193 hours) |
20 bytes per 1 timer in SVA |
Counter |
No limitation. Count range: -32768~32767 |
8 bytes per 1 counter in SVA |
Operation mode |
RUN, STOP, PAUSE, DEBUG |
|
Data retention at power failure |
Set to 'Retain' at data declaration |
|
Number of program blocks |
100 |
|
Program type |
Task |
Scan |
100 - (Number of program blocks in task) |
|
Time-driven |
8 |
8 in total |
Externa |
8 |
Internal |
8 |
Initialization |
1 (_INIT) |
Self-diagnostic function |
Watchdog timer, Memory error, I/O error, etc |
|
Restart mode |
Cold, Warm |
|
Built-in function |
PID control |
Control by function block, Autotuning, Forward/Reverse operation, Manual output, Operation scan time setting |
|
Cnet interface |
Dedicated, Modbus, User-defined protocol |
|
HSC |
Counting speed |
1-phase 16kHz, 2-phase 8kHz |
|
Counting method |
1-phase up/down counter (up/down: selection by program) 1-phase up/down counter (up/down: selection by B-phase) 2-phase up/down counter (up/down: Automatic selection by phase difference) |
|
Multiplication |
1, 2 or 4 |
|
Task program running |
Task program running when the current value of HSC reaches the setting value |
|
Pulse catch |
Min. pulse width: 2ms, Maximum 8 points available to use |
|
Pulse output |
2kHz, 1Ch |
|
External interrupt Input |
8 points |
|
Input filter function |
0~15ms (Setting by 1ms) |
|