K200S/K300S

Powerful & compact module-type PLC K200S & K300S are module-type PLC that consist of various modules including basic module(CPU, Power, I/O), communication module and special module. And through various modules, user can configure the optimum system for industry environment.
Features
K200S Features
- Small- and medium-scale control with 384 points
- High-speed processing (0.5㎲/step)
- On-line editing
- Change I/O value by force
- Small- and medium-sized manufacture line control by network
- Various special modules: analog, HSC, positioning, etc
- Built-in flash memory
K300S Features
- Small- and medium-scale control with 1,024 points
- High-speed processing: 0.2㎲/step
- On-line editing
- Change I/O value by force
- Small- and medium-sized manufacture line control by network
- Downsizing and high performance
- Various special modules: analog, HSC, PID, positioning, etc
Specification
Item |
K3P-07AS |
K3P-07BS |
K3P-07CS |
Operation method |
Cyclic execution of stored program, Time-driven operation, Interrupt task operation |
I/O control method |
Scan synchronized batch processing method (Refresh method), Direct method by program |
Program language |
Mnemonic, Ladder |
Number of instructions |
Basic |
30 |
Application |
218 |
Processing speed |
0.5㎲/Step |
Program memory capacity |
7Ksteps |
Memory device |
P (I/O Relay) |
P0000~P31F (512 points) *1) |
M (Auxiliary relay) |
M0000~M191F (3,072 points) |
K (Keep relay) |
K0000~K031F (512 points) |
L (Link relay) |
L0000~L063F (1,024 points) |
F (Special relay) |
F000~F063F (1,024 points) |
T (Timer) |
100ms |
T000~T191 (192 points) |
10ms |
T192~T255 (64 points) |
C (Counter) |
C000~C255 (256 points) |
S (Step controller) |
S00.00~S99.99 (100 x 100) |
D (Data register) |
D0000~D4999 (5,000 words) |
Timer type |
ON Delay, OFF Delay, Integration, Monostable, Retriggerable timer |
Counter type |
Up, Down, Up-Down, Ring counter |
Special function |
On-line editing, Change I/O value by force |
Operation mode |
Run, Stop, Pause, Debug |
Max. expansion stage |
Main base only *2) |
Self-diagnosis functions |
Watchdog timer, Memory error, I/O error, Batter error, Power supply error |
Built-in functions |
Cnet (RS-232C) |
PID control Cnet (RS-422/485)RTC function |
PID control Cnet (RS-232C)HSC (50kHz)RTC function |
*1) With a 32-point I/O installation, P area is P0000~P023F and the rest of it is available to Use as internal memory.
*2) The suitable power module for GM6-B12M is GM6-PAFC, which can't support an analog Module. For analog modules or TC module, you are supposed to use GM6-PAFB or GM6-PDFB considering internal current consumption of each module. Communication modules are not to be installed in after slot number 7.
Item |
K4P-15AS |
Operation method |
Cyclic execution of stored program, Time-driven operation, Interrupt task execution |
Programming language |
Ladder, Mnemonic |
I/O control method |
Scan synchronized batch processing method (Refresh method), Direct method by program |
Number of Instructions |
Basic |
30 |
Application |
218 |
Processing speed |
0.2 ㎲/Step |
Program memory capacity |
15K steps |
Data Type |
P (I/O relay) |
P0000~P31F (1,024 points) |
M (Aux. relay) |
M0000~M191F (3,072 points) |
K (Keep relay) |
K0000~K031F (512 points) |
L (Link relay) |
L0000~L063F (1,024 points) |
F (Special relay) |
F000~F063F (1,024points) |
T (Timer) |
100ms |
T000~T191 (192points) |
10ms |
T192~T255 (64points) |
C (Counter) |
C000~C255 (256points) |
S (Step controller) |
S00.00~S99.99 (100 x 100 step) |
D (Data register) |
D0000~D4999 (5,000 words) |
Timer type |
ON Delay, OFF Delay, Integration, Monostable, |
Retriggerable timer |
Counter type |
Up, Down, Up-Down, Ring counter |
Special functions |
RTC, On-line editing, Change I/O value |